ID-FLX Lite & Telecom Global Guide
146
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 3600 [s]
Default value 10 -
Step 1
Comm object 9276 Related applications
Description
Delay for Wrn/Sd AIN5 alarm.
AIN5 Del
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] NORMAL, CLASS C [-]
Default value NORMAL -
Step -
Comm object 13373 Related applications
Description
NORMAL
Protection behaves according to the standard configuration of Wrn/Sd alarm in
LiteEdit AINx configuration screen. Default state.
CLASSC
The protection is type Running only” and does not depend on Running only tick in
LiteEdit AINx Alarm properties configuration window. Protection (Class C) is
working after AINx Del or sooner when appropriate value increases over AINx Wrn
limit +3 seconds - after engine start. Warning/ShutdDown protection is activated
with fix delay 0.5s.
Note: Class C protection is working and corresponding setpoints are visible only when corresponding
AIN is configured in Modify->Alarm properties-> Direction-> Window prot.
AIN5 Eval
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 10000 [U17]
Default value 20 -
Step 1
Comm object 13353 Related applications
Description
Low Warning limit level for AIN5.
AIN5 LowWrn
6 back to List of setpoints