7 Technical data
Power supply range
8-36 VDC
Power consumption
394 mA / 8 VDC
255 mA / 12 VDC
140 mA / 24 VDC
97 mA / 36 VDC
RTC battery
Replaceable
Fusing
Power terminal max. 3 A
E-Stop max.12 A
Fusing E-Stop
12 A
Max. Power
Dissipation
3.5 W
Power supply
Operating
temperature
-20 ˚C to +70 ˚C
Operating
temperature for Low
Temp. version
-40 ˚C to +70 ˚C
Storage temperature
-30 ˚C to +80 ˚C
Protection degree
(front panel)
IP 65
Operating humidity
95 % w/o condensation
Vibration
5-25 Hz, ± 1.6 mm
25-100 Hz, a = 4 g
Shocks
a = 500 m/s
2
Surrounding air temperature rating 70°C
Suitable for pollution degree 3
Operating conditions
Max. output current
250 mA / 36 V
Charging fail
threshold
Adjustable
D+ terminal
Measurement
inputs
3ph-n Gen voltage , 3ph-n
Mains
Measurement
range
277V / 480VAC (EU)
346V / 600VAC (US/Canada)
Linear
measurement and
protection range
381V / 660V
Accuracy
1 %
Frequency range
40-70 Hz (accuracy 0.1 Hz)
Input impedance
0.72 MΩ ph-ph , 0.36 MΩ ph-n
Voltage measurement
USB port
non-isolated
CAN 1
CAN bus, 250 kbps, max 200
m, 120 Ω termination option,
non- isolated
Communications
Measurement inputs
3ph Gen current
Measurement range
5 A
Max. allowed
current
10 A
Accuracy
1.5 % for full temperature range
(1 % from 0 ˚C to 50 ˚C)
Input impedance
< 0.1 Ω
Current measurement
Number
7, non-isolated
Close/Open indication
0-2 VDC close contact
6-36 VDC open contact
Binary inputs
Low current
5 low current output, non-
isolated
0.5 A
switching to positive supply
voltage, BATT+
High current
2 high current output, non-
isolated
5 A (60 °C), 4 A (70 °C)
switching to positive supply
voltage, BATT+
Binary outputs
Number
4, non-isolated
Type
Resistive
Resolution
0.1 Ω
Range
0-2500 Ω
Input impedance
170 Ω
Accuracy
±2 % from value in range 0-
2500 Ω
±1.5 kΩ in range 2.5-15 kΩ
Analog inputs
InteliLite Global Guide
165