(PAGE 633) is de-energized and a pause with length determined by Cranking Fail Pause (page 206) will
follow. PRESTART (PAGE 621) and GLOW PLUGS (PAGE 609) outputs are active during the pause. After the
pause has elapsed, the next start attempt is executed. The number of start attempts is given by the setpoint
Cranking Attempts (page 205).
Once the engine is started, the Idle period follows. The binary output IDLE/NOMINAL (PAGE 612) remains
inactive (as it was during the start). The idle period duration is adjusted by the setpoint Idle Time (page
214). When controller is in the MANmode, it is possible to finish the Idle Time (page 214) count down by
pushing the Start button.
After the idle period has finished, the output IDLE/NOMINAL (PAGE 612) is activated and the start-up
sequence is finished. The Stabilization (page 107) phase follows.