InteliLite Global Guide
621
LBO: P
Related FW 1.9.0 Related applications AMF, MRS
Comm object 290
Description
This is an output from the Power switch function. The behavior of the switch depends on the adjustment of
the setpoints Power Switch On (page 238) and Power Switch Off (page 239). When the dummy load
function is used the switching ON of Power switch is block when the engine isn’t running and is allowed 30 s
after start of the engine.
Image 8.199 Power Switch
Note: Setpoints Power Switch On (page 238) and Power Switch Off (page 239) are invisible until
configuration of this LBO.
Power Switch
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 36
Description
This output can be used for control of any device, which has to be activated just before start. The output is
closed for time period of Prestart Time (page 207). The output opens 100 ms before the STARTER (PAGE
633) output closes.
Image 8.200 Engine start
Prestart