InteliLite Global Guide
622
Related FW 1.9.0 Related applications AMF, MRS
Comm object 9981
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 40. Limits for this protection are adjusted by setpoints
Analog Protection 19 Wrn (page 295) and Analog Protection 19 Sd (page 296). Delay is adjusted by
setpoint Analog Protection 19 Delay (page 296).
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Protection types
Note: This parameter has to be adjusted via InteliConfig.
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Alarm
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Note: This parameter has to be adjusted via InteliConfig.
AIN Prot19
6 back to Logical analog inputs alphabetically

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals