InteliLite Global Guide
568
Related FW 1.9.0 Related applications AMF, MRS
Comm object 40
Description
This output is dedicated for coolant pump control. It is closed in the moment the gen-set is started and
remains closed until the gen-set is stopped and After Cooling Time (page 204) elapses or the cranking
pause or the Emergency Stop occurs or the controller is switched to OFF mode.
Image 8.160 Cooling Pump
Cooling Pump
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 74
Description
The output closes when gen-set is in Cooling state.
Cooling
6 back to Logical binary outputs alphabetically
LBO: D
Related FW 1.9.0 Related applications AMF, MRS
Comm object 2097
Description
This LBO is active when there is Dual Operation Fail (page 665) alarm in alarmlist.
Dual Operation Error
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 2096
Description
This LBO is active when there is not Dual Operation Fail (page 665) alarm in alarmlist.
Dual Operation OK
6 back to Logical binary outputs alphabetically

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals