InteliLite Global Guide
586
This output can be used for control of any device, which has to be activated just before start. The output is
closed for time period of Prestart Time (page 191). The output opens 100 ms before the STARTER (PAGE
597) output closes.
Image 8.181 Engine start
When the Prestart Time (page 191) is longer than Cranking Fail Pause (page 190) then the Prestart
Time (page 191) in Cranking Fail Pause (page 190) is long as Cranking Fail Pause (page 190) minus
100ms.