EasyManuals Logo

ComAp InteliLite AMF25 User Manual

ComAp InteliLite AMF25
735 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #585 background imageLoading...
Page #585 background image
InteliLite Global Guide
585
Related FW 1.9.0 Related applications AMF, MRS
Comm object 286
Description
Output has no function.
Not Used
6 back to Logical binary outputs alphabetically
LBO: P
Related FW 1.9.0 Related applications AMF, MRS
Comm object 290
Description
This is an output from the Power switch function. The behavior of the switch depends on the adjustment of
the setpoints Power Switch On (page 223) and Power Switch Off (page 224). When the dummy load
function is used the switching ON of Power switch is block when the engine isn’t running and is allowed 30 s
after start of the engine.
Image 8.180 Power Switch
Note: Setpoints Power Switch On (page 223) and Power Switch Off (page 224) are invisible until
configuration of this LBO.
Power Switch
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 36
Description
Prestart

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals