InteliLite Global Guide
662
Alarm Type Warning
Alarmlist message Wrn Maintenance 2
Alarm evaluated All the time
Related applications AMF, MRS
Description
Adjust the setpoint Maintenance Timer 2 (page 220) to the interval of the next
maintenance check. The value of the setpoint will count down while the engine is
running and if reaches zero, this alarm will be issued. The alarm message will
remain in the alarm list (even if the controller is switched off and on again) until the
setpoint is re-adjusted to a positive value.
Wrn Maintenance 2
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Maintenance 3
Alarm evaluated All the time
Related applications AMF, MRS
Description
Adjust the setpoint Maintenance Timer 3 (page 220) to the interval of the next
maintenance check. The value of the setpoint will count down while the engine is
running and if reaches zero, this alarm will be issued. The alarm message will
remain in the alarm list (even if the controller is switched off and on again) until the
setpoint is re-adjusted to a positive value.
Wrn Maintenance 3
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Oil Pressure
Alarm evaluated Gen-set is running
Related applications AMF, MRS
Description
This alarm indicates that the oil pressure is lower than the pressure set in Oil
Pressure Wrn (page 208) setpoint.
Wrn Oil Pressure
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Overload
Alarm evaluated All the time
Related applications AMF, MRS
Description
The alarm is issued when the gen-set power is over the limit for time period longer
than the delay. The following setpoints are related to it:
Overload Wrn (page 227) adjusts the overload limit.
Overload Delay (page 227) Overload Del adjusts the delay.
Wrn Overload
6 back to List of alarms level 1