InteliLite Global Guide
661
Alarm Type Warning
Alarmlist message Wrn Generator > Frequency
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Overfrequency Wrn (page 233)
Generator <> Frequency Delay (page 234)
Wrn Generator > Frequency
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Generator < Frequency
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Underfrequency Wrn (page 234)
Generator <> Frequency Delay (page 234)
Wrn Generator < Frequency
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Check DPF Status
Alarm evaluated When ECU is configured
Related applications AMF, MRS
Description
This alarm occurs when ECU send alarm message about Tier IV protection.
Note: Tier IV protection have to be supported by ECU.
Wrn Check DPF Status
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Maintenance 1
Alarm evaluated All the time
Related applications AMF, MRS
Description
Adjust the setpoint Maintenance Timer 1 (page 219) to the interval of the next
maintenance check. The value of the setpoint will count down while the engine is
running and if reaches zero, this alarm will be issued. The alarm message will
remain in the alarm list (even if the controller is switched off and on again) until the
setpoint is re-adjusted to a positive value.
Wrn Maintenance 1
6 back to List of alarms level 1