InteliLite Global Guide
604
Gas:
The output closes together with binary output IGNITION (PAGE 612) when engine RPM exceed 30 RPM (fix
value).
Image 8.173 Fuel Solenoid 3
The output opens when:
Emergency Stop comes
cooled gen-set is stopped
in pause between repeated starts
6 back to Logical binary outputs alphabetically
LBO: G
Related FW 1.9.0 Related applications AMF, MRS
Comm object 41
Description
The output controls the generator circuit breaker. Its state represents the breaker position requested by the
controller. The breaker must react within 5 seconds to a close or open command, otherwise an alarm is
issued.
Note: InteliLite controllers can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
GCB Close/Open