InteliLite Global Guide
600
LBO: T
Related FW 1.9.0 Related applications AMF, MRS
Comm object 563
Description
This is an output from the Temperature switch function. The behavior of the switch depends on the
adjustment of the setpoints Temperature Switch On (page 212) and Temperature Switch Off (page 213).
Image 8.189 Temperature Switch
Note: Setpoints Temperature Switch On (page 212) and Temperature Switch Off (page 213) are
invisible until configuration of this LBO.
Temperature Switch
6 back to Logical binary outputs alphabetically
LBO: V
Related FW 1.9.0 Related applications AMF, MRS
Comm object 38
Description
This logical binary output is activated at the beginning of start procedure together with PRESTART (PAGE 585)
LBO. Ventilation output is deactivated when engine stops revolving.
Ventilation LBO is also deactivated immediately when EMERGENCY STOP (PAGE 528) (or E-Stop) is
activated or when controller is switched to OFF mode.
Note: The output is intended for control of an engine room ventilation fan, engine container ventilation
fan, container louvres or similar running gen-set technology.
Ventilation
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 2090
Description
This logical binary output is activated on falling edge of VENTILATION (PAGE 600) LBO (when engine stops).
The pulse duration is adjusted by Ventilation Pulse Time (page 226) setpoint.
Ventilation Off Pulse