InteliLite Global Guide
578
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1263
Description
This output is active when at least one generator voltage BOC or Sd alarm is present in alarmlist or isn’t
confirm.
AL Gen Voltage
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 197
Description
Output for signaling Mains Failure. This output is active when at least one mains frequency BOC or Sd alarm
or at least one mains voltage BOC or Sd alarm is present in alarmlist or isnt confirmed.
AL Mains Fail
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF
Comm object 1271
Description
This output is active when at least one mains frequency BOC or Sd alarm is present in alarmlist or isn’t
confirm.
AL Mains Frequency
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF
Comm object 1270
Description
This output is active when at least one mains voltage BOC or Sd alarm is present in the alarmlist or isn’t
confirm.
AL Mains Voltage
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1254
Description
This output is active when the Alarm Maintenance 1 is present in the alarmlist. It means that counter of
maintenance is on zero or the Alarm Maintenance 1 isn’t confirm.