InteliLite Global Guide
579
Related FW 1.9.0 Related applications AMF, MRS
Comm object 77
Description
This output is active when the generator voltage, frequency and voltage unbalance is within limits. It is
deactivated:
immediately when the voltage/frequency/voltage unbalance gets out of limits (when GCB is not
closed)
or
with an appropriate delay after the voltage/frequency/voltage unbalance has got out of limits (when
GCB is closed)
Generator Healthy
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1252
Description
This output is dedicated for diesel engine only. This output will close for exact time pre-set by setpoint Glow
Plugs Time (page 192) before every starting attempt. The output opens in same time as the STARTER
(PAGE 597) output closes (100 ms after PRESTART (PAGE 585) output opens).
Image 8.174 Glow Plugs
Glow Plugs

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals