598
Related FW 1.9.0 Related applications AMF, MRS
Comm object 25
Description
Output is active for 1 second after STOP SOLENOID (PAGE 598) output activation. This signal is sent to ECU
in case of engine stop request.
Image 8.186 Stop Pulse
Stop Pulse
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 23
Description
This output is dedicated to control the stop solenoid (valve). The output closes when an engine stop
command is received and is deactivated 12 s after last running engine indication went off, i.e. engine is
stopped.
Image 8.187 Stop Solenoid 1
Stop Solenoid