InteliLite Global Guide
703
14
GSM modem did not accepted particular initialization command, possibly caused by locked
SIM card
15 Unknown modem
16 Bad answer to complement initialization string
17 Not possible to read GSM signal strength
18 CDMA modem not detected
19 No CDMA network
20 Unsuccessful registration to CDMA network
21 SIMCom/ME909s: can´t read FW version
22 SIMCom: GSM signal not found
23 SIMCom: can´t detect module speed
24 SIMCom: HW reset issued
25 PUK is required
26 Error of SIM card detected
27 ME909s: can't set module bps
28 ME909s: can't set link configuration
29 ME909s: can't do power-off
30 ME909s: can't do power-on
31 ME909s: can't do hardware reset
32 ME909s: ME909s not started
33 ME909s: switch off issued
34 ME909s: switch on issued
35 ME909s: HW reset issued
36 ME909s: can't switch echo off
37 ME909s: can't find out state of registration
38 ME909s: GSM signal not found
39 ME909s: no SIM memory for SMS
40 ME909s: waiting for registration
41 Can't read operator name
42 ME909s: can't set flow control
43 APN not typed
255 Only running communication is needed to indicate
AirGate Diag – Diagnostic Code for AirGate connection
Code Description
0 Waiting for connection to AirGate Server
1 Controller registered, waiting for authorization
2 Not possible to register, controller blacklisted
3 Not possible to register, server has no more capacity
4 Not possible to register, other reason
5 Controller registered and authorized