InteliLite Global Guide
220
Setpoint group Engine settings Related FW 1.9.0
Range [units] -10 000 ... 9 999 [h] / Disabled
Default value 1 000 h Alternative config NO
Step 1 h
Comm object 11617 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maintenance timer 2 counts down when engine is running. If reaches zero, an alarm appears, but the timer
still counting down into negative values. When the value 10000 is set, than the Maintenance function is
disabled and counter does not count. Counter value disappear from controllers statistics.
Maintenance Timer 2
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] -10 000 ... 9 999 [h] / Disabled
Default value 1 000 h Alternative config NO
Step 1 h
Comm object 11618 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maintenance timer 3 counts down when engine is running. If reaches zero, an alarm appears, but the timer
still counting down into negative values. When the value 10000 is set, than the Maintenance function is
disabled and counter does not count. Counter value disappear from controllers statistics.
Maintenance Timer 3
6 back to List of setpoints
Subgroup: Battery Protections
Setpoint group Engine settings Related FW 1.9.0
Range [units] 8,0 V .. Battery Overvoltage (page 221) [V]
Default value 18,0 V Alternative config NO
Step 0,1 V
Comm object 8387 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Warning threshold for low battery voltage.
Battery Undervoltage
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65