InteliLite Global Guide
185
Setpoint group Basic settings Related FW 1.9.0
Range [units] Disabled / 1 .. 599 [s]
Default value 10 s Alternative config NO
Step 1 s
Comm object 8264 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Setting of horn behavior.
Disabled Disabling the Horn sounding function
1 .. 599 [s]
Timeout for HORN (PAGE 581) binary output. The HORN (PAGE 581) output is opened when
this timeout elapsed.
Note: Horn timeout starts again from the beginning if a new alarm appears before previous Horn timeout
has elapsed.
Horn Timeout
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.9.0
Range [units] Disabled / 1 - 360 [min]
Default value Disabled Alternative config NO
Step 1 min
Comm object 8548 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
The controller is switched to Zero Power Mode when there is no user interaction with the controller for the
preset time period. Zero Power Mode is disabled in AMF automatic mode. For the controller wake up press
button Start or activate Binary Input 1. The controller will not switch to Zero Power Mode if generator is
running. In Zero Power Mode binary outputs go to high impedance.
Note: Power consumption of controller in Zero Power Mode is 0 mA. Controller is internally
disconnected from power supply.
Zero Power Mode
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals