InteliLite Global Guide
237
Setpoint group Engine settings Related FW 1.9.0
Range [units] Battery Undervoltage (page 236) .. 40,0 [V]
Default value 36,0 V Alternative config NO
Step 0,1 V
Comm object 9587 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Warning threshold for high battery voltage.
Battery Overvoltage
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 600 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 8383 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Battery Undervoltage (page 236) and Battery Overvoltage (page 237) protection.
Battery <> Voltage Delay
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 15 [min]
Default value 5 min Alternative config NO
Step 1 min
Comm object 11374 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Conditioned with LBI BATTERY CHARGER (PAGE 526)
Description
Delay for LBI BATTERY CHARGER (PAGE 526).
Battery Charger Fail Delay
6 back to List of setpoints