InteliLite Global Guide
238
Subgroup: Pulse Counters
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 ... 1 000 [-]
Default value 1 Alternative config NO
Step 1
Comm object 10994 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Only if LBI PULSE COUNTER 1 (PAGE 562) is configured
Description
This setpoint adjusts the rate of increasing of the Pulse Counter 1 function. The module counts pulses at the
input PULSE COUNTER 1 (PAGE 562) and if the input pulses counter reaches value given by this setpoint, the
counter value Pulse Counter 1 (page 496) is increased by 1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Conversion Coefficient Pulse 1
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 ... 1 000 [-]
Default value 1 Alternative config NO
Step 1
Comm object 10995 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Only if LBI PULSE COUNTER 2 (PAGE 562) is configured
Description
This setpoint adjusts the rate of increasing of the Pulse Counter 2 function. The module counts pulses at the
input PULSE COUNTER 2 (PAGE 562) and if the input pulses counter reaches value given by this setpoint, the
counter value Pulse Counter 2 (page 496) is increased by 0,1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Conversion Coefficient Pulse 2
6 back to List of setpoints
Subgroup: Power switch
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 32 000 [kW]
Default value 100 kW Alternative config NO
Step 1 kW
Comm object 11658 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if the logical binary output POWER SWITCH (PAGE 621) is configured.
Power Switch On