InteliLite Global Guide
562
Related FW 1.9.0 Related applications AMF, MRS
Comm object 87
Description
This is the input of the Pulse Counter 1 function. The module counts pulses at the input and if the input
pulses counter reaches value given by the setpoint Conversion Coefficient Pulse 1 (page 238) the
counter value Pulse Counter 1 (page 496) is increased by 1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Pulse Counter 1
6 back to Logical binary inputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 88
Description
This is the input of the Pulse Counter 2 function. The module counts pulses at the input and if the input
pulses counter reaches value given by the setpoint Conversion Coefficient Pulse 2 (page 238) the
counter value Pulse Counter 2 (page 496) is increased by 0,1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Pulse Counter 2
6 back to Logical binary inputs alphabetically
LBI: R
Related FW 1.9.0 Related applications AMF, MRS
Comm object 679
Description
When this binary input is activated, the controller sends request to inhibit regeneration of DPF (diesel
particulate filter) to ECU.
Note: ECU with Tier IV support is required for proper functionality.
Regeneration Inhib
6 back to Logical binary inputs alphabetically