InteliLite Global Guide
524
Related FW 1.9.0 Related applications AMF, MRS
Comm object 9952
Description
This binary input is for general input function used as alarm.
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
BIN Protection 48
6 back to Logical binary inputs alphabetically
LBI: C
Related FW 1.9.0 Related applications AMF, MRS
Comm object 946
Description
Logical binary input CHOKE INHIBIT prevent Choke functionality when logical binary output CHOKE (PAGE
567) is activated. If CHOKE INHIBIT is activated when CHOKE LBO is active, CHOKE LBO is deactivated
immediately and vice versa if LBI CHOKE INHIBIT is deactivated and LBO CHOKE should be active then is
activated.
Choke Inhibit