InteliLite Global Guide
559
Related FW 1.9.0 Related applications AMF, MRS
Comm object 109
Description
Use this binary input with binary input LANG SELECTION 1 (PAGE 558) and LANG SELECTION 2 (PAGE 558) to
choose required language of controller. The system is based on binary numbers.
Binary input Binary number Active language
Language Selection 1 is active 1 First language (English)
LANG SELECTION 2 (PAGE 558) is active 2 Second language
Language Selection 1 and LANG SELECTION
2 (PAGE 558) are active
3 Third language
Lang Selection 3 (page 1) is active 4 Fourth language
LANG SELECTION 1 (PAGE 558) and Lang
Selection 3 (page 1) are active
5 Fifth language
Lang Selection 3
6 back to Logical binary inputs alphabetically
LBI: M
Related FW 1.9.0 Related applications AMF
Comm object 622
Description
If the input is closed, the automatic start of the gen-set at Mains failure is blocked. In case of running gen-set
in AUTO mode, timer Mains Return Delay (page 255) is started and when it elapses GCB is opened, gen-
set goes to cooling procedure and stops. When GCB is opened after Transfer Delay (page 256) the MCB is
closed.
Note: This input simulates healthy Mains.
Mains Fail Block
6 back to Logical binary inputs alphabetically
Related FW 1.9.0 Related applications AMF
Comm object 194
Description
This binary input has the same function as MCB button on the InteliLite front panel. It is evaluated in
MAN mode only.
MCB Button
6 back to Logical binary inputs alphabetically