InteliLite Global Guide
256
Setpoint group AMF settings Related FW 1.9.0
Range [units] 0,0 .. 600,0 [s]
Default value 1,0 s Alternative config NO
Step 0,1 s
Comm object 8303 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Operation Mode (page 199)
Description
Delay after GCB opening to MCB closing during the return procedure. Delay after MCB opening to GCB
closing if the setpoint MCB Opens On (page 263) is set to GENRUN.
The time charts bellow show recommended setting of Transfer Delay setpoint.
If the Transfer Delay setpoint is set shorter than the time required for opening of the circuit breaker, the
controller closes GCB CLOSE/OPEN (PAGE 604) output straight away (100 ms) after the MCB FEEDBACK
(PAGE 560) input deactivates.
Image 8.21 Transfer Delay 1
If some delay between MCB FEEDBACK (PAGE 560) deactivation and closing of GCB CLOSE/OPEN (PAGE
604) output is required, then the Transfer Delay must be set to sum of “MCB opening” + “Delay” time.
Transfer Delay