InteliLite Global Guide
552
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1291
Description
This output is active when the Sd Start Fail (page 682) alarm is present in the alarmlist or isn’t confirm.
AL Start Fail
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 339
Description
This output is active when the Wrn Stop Fail (page 663) alarm is present in the alarmlist or isn’t confirm.
AL Stop Fail
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1296
Description
This output is active when the Sd Underspeed (page 682) alarm is present in the alarmlist or isn’t confirm.
AL Underspeed
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 2
Description
The output is designed to be used as external alarm indication such as a red bulb in the control room etc. The
output is active when at least one unconfirmed alarm is present in the alarmlist and remains active until
confirmation of alarm.
Alarm
6 back to Logical binary outputs alphabetically