InteliLite Global Guide
535
Related FW 1.9.0 Related applications AMF, MRS
Comm object 88
Description
This is the input of the Pulse Counter 2 function. The module counts pulses at the input and if the input
pulses counter reaches value given by the setpoint Conversion Coefficient Pulse 2 (page 223) the
counter value Pulse Counter 2 (page 470) is increased by 0,1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Pulse Counter 2
6 back to Logical binary inputs alphabetically
LBI: R
Related FW 1.9.0 Related applications AMF, MRS
Comm object 679
Description
When this binary input is activated, the controller sends request to inhibit regeneration of DPF (diesel
particulate filter) to ECU.
Note: ECU with Tier IV support is required for proper functionality.
Regeneration Inhib
6 back to Logical binary inputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 620
Description
The controller is switched to the AUTO mode (there are four modes OFF / MAN / AUTO / TEST) when this
binary input is closed. When opens controller is switched back to previous mode.
This binary input has the lowest priority from Remote OFF / MAN / AUTO / TEST binary inputs
Remote control priority:
Remote OFF (Highest priority)
Remote TEST
Remote MAN
Remote AUTO (Lowest Priority)
Remote AUTO
6 back to Logical binary inputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 4
Description
If the input is active, the controller will not accept any actions regarding the system control – e.g. writing of
commands and setpoint changes via remote communication interfaces.
Remote CtrlLock
6 back to Logical binary inputs alphabetically