InteliLite Global Guide
564
LBO: B
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1374
Description
This output is closed, when Binary Input 1 is active and open when Binary Input 1 is inactive. When Binary
Input 1 is used for BIN protection function then this output is closed when BIN protection alarm is in
Alarmlist.
Note: When LBI 1 is used like protection, then state of this LBO is connected with this protection e.g.
when LBI is inactive but alarm of protection is not confirm in alarmlist, LBO is still active.
Image 8.153 Binary Input 1 Status
BIN 1 Status
6 back to Logical binary outputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1375
Description
This output is closed, when Binary Input 2 is active and open when Binary Input 2 is inactive. When Binary
Input 2 is used for BIN protection function then this output is closed when BIN protection alarm is in
Alarmlist.
Note: When LBI 2 is used like protection, then state of this LBO is connected with this protection e.g.
when LBI is inactive but alarm of protection is not confirm in alarmlist, LBO is still active.
Image 8.154 Binary Input 2 Status
BIN 2 Status
6 back to Logical binary outputs alphabetically

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals