InteliLite Global Guide
554
Related FW 1.9.0 Related applications AMF, MRS
Comm object 40
Description
The shutdown procedure will start immediately when this input is activated. Input is inverted (NC = normaly
closed) in default configuration.
Note: In case of controller hardware or software fail, safe stop of the engine doesn’t have to be ensured.
To back-up the Emergency Stop function it is recommended to connect separate circuit for
disconnection of Fuel Solenoid and Starter signals.
For more detail see chapter recommended wiring.
Emergency Stop
6 back to Logical binary inputs alphabetically
LBI: F
Related FW 1.9.0 Related applications AMF, MRS
Comm object 191
Description
Binary input has the same function as Fault Reset button on the InteliLite front panel.
Fault Reset Button
6 back to Logical binary inputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 680
Description
When this binary input is activated, the controller send request for force regeneration of DPF (diesel
particulate filter) to ECU.
Note: ECU with Tier IV support is required for proper functionality.
Force Regeneration