InteliLite Global Guide
525
6 back to Logical binary inputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 625
Description
Binary input for COOLANT TEMP (PAGE 631) protection.
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Coolant Temp
6 back to Logical binary inputs alphabetically