InteliLite Global Guide
526
Related FW 1.9.0 Related applications AMF
Comm object 211
Description
This binary input can allow or block the AMF start. In case of running gen-set in AUTO mode gen-set goes to
cooling procedure and stops.
AMF Start Block
6 back to Logical binary inputs alphabetically
LBI: B
Related FW 1.9.0 Related applications AMF, MRS
Comm object 623
Description
When binary input is active and its delay Battery Charger Fail Delay (page 237) is out of time then alarm
Battery Charger Fail (page 689) is activated, written into history log and logical binary output AL BATTERY
CHARGER (PAGE 572) is activated.
Battery Charger
6 back to Logical binary inputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 9999
Description
This binary input is for general input function used as alarm.
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
BIN Protection 1
6 back to Logical binary inputs alphabetically