Setpoint group Engine settings Related FW 1.9.0
Range [units] Fuel Pump On (page 233) .. 100 [%]
Default value 90 % Alternative config NO
Step 1 %
Comm object 10101 Related applications AMF, MRS
Config level Advanced
Setpoint visibility
Visible only if the logical binary output FUEL PUMP (PAGE 602) is configured and
logical binary input FUEL PUMP ON/OFF (PAGE 555) isn’t configured
Description
Threshold level for switching the binary output FUEL PUMP (PAGE 602) off.
Image 8.14 Fuel Pump Off
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 555) is configured then binary
output FUEL PUMP (PAGE 602) is control by this binary input. Setpoints Fuel Pump On (page
233) and Fuel Pump Off are not evaluated!
Note: Value from analog input has higher priority than ECU.
Note: This setpoint is visible only if the logical binary output FUEL PUMP (PAGE 602) is configured.
Fuel Pump Off