InteliLite Global Guide
233
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 600 [s]
Default value 5 s Alternative config NO
Step s
Comm object 14683 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
When the value of fuel drop per hour is higher than Maximal Fuel Drop (page 232) this delay stars count
down. After count down of this delay alarm Wrn Fuel Theft (page 694) is activated.
Maximal Fuel Drop Delay
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. Fuel Pump Off (page 234) [%]
Default value 20 % Alternative config NO
Step 1 %
Comm object 10100 Related applications AMF, MRS
Config level Advanced
Setpoint visibility
Visible only if the logical binary output FUEL PUMP (PAGE 602) is configured and
logical binary input FUEL PUMP ON/OFF (PAGE 555) isn’t configured
Description
Threshold level for switching the binary output FUEL PUMP (PAGE 602) on.
Image 8.13 Fuel Pump On
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 555) is configured then binary
output FUEL PUMP (PAGE 602) is control by this binary input. Setpoints Fuel Pump On and
Fuel Pump Off (page 234) are not evaluated!
Note: Value from analog input has higher priority than ECU.
Note: This setpoint is visible only if the logical binary output FUEL PUMP (PAGE 602) is configured.
Fuel Pump On
6 back to List of setpoints