694
Alarm Type Warning
Alarmlist message Wrn Fence 2 Alarm
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm evaluates the GPSposition of gen-set. The following setpoint are
related to it:
Geo-Fencing (page 348)
Fence 2 Protection (page 350)
Fence Radius 2 (page 347)
Wrn Fence 2 Alarm
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Fuel Level
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the fuel level is lower than the level set in Fuel Level
Wrn (page 230) setpoint.
Wrn Fuel Level
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Fuel Theft
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm occurs when the fuel level value measured at relevant AI (Fuel Level)
drops faster than is the limit adjusted by setpoint Maximal Fuel Drop (page 232).
Wrn Fuel Theft
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Generator L1 > Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase voltage in phase 1. The following
setpoints are related to it:
Generator Overvoltage Wrn (page 246)
Generator <> Voltage Delay (page 247)
Wrn Generator L1 > Voltage
6 back to List of alarms level 1