InteliLite Global Guide
247
Setpoint group Generator settings Related FW 1.9.0
Range [units]
Generator Undervoltage BOC (page 246) .. Generator Overvoltage Wrn (page
246) [%]
Default value 70 % Alternative config NO
Step 1 % of Nominal Voltage Ph-N (page 195) or Nominal Voltage Ph-Ph (page 195)
Comm object 9687 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator undervoltage protection. All three phases are checked. Minimum out of three is used.
Note: Phase to phase and phase to neutral voltages are used for this protection.
Generator Undervoltage Wrn
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.9.0
Range [units] 0,0 .. 600,0 [s]
Default value 3,0 s Alternative config NO
Step 0,1 s
Comm object 9103 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Generator Overvoltage Sd (page 245), Generator Overvoltage Wrn (page 246), Generator
Undervoltage BOC (page 246) and Generator Undervoltage Wrn (page 247) protection.
Generator <> Voltage Delay
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.9.0
Range [units] 1 .. 200 [%] of Nominal Voltage Ph-Ph (page 195)
Default value 10 % Alternative config NO
Step 1 % of Nominal Voltage Ph-Ph (page 195)
Comm object 8288 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Conditioned by the setpoint Connection type (page 193)
Description
Threshold for generator voltage unbalance alarm.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Voltage Unbalance BOC
6 back to List of setpoints