InteliLite Global Guide
245
Setpoint group Generator settings Related FW 1.9.0
Range [units] 1 .. 200 [%] of Nominal Current (page 191)
Default value 50 % Alternative config NO
Step 1 % of Nominal Current (page 191)
Comm object 8284 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Conditioned by the setpoint Connection type (page 193)
Description
Threshold for generator current asymmetry (unbalance).
Protection is BOC (Breaker Open and genset Cooldown).
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Current Unbalance BOC
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.9.0
Range [units] 0,0 .. 600,0 [s]
Default value 5,0 s Alternative config NO
Step 0,1 s
Comm object 8285 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Conditioned by the setpoint Connection type (page 193)
Description
Delay for Current Unbalance BOC (page 245) protection.
Current Unbalance BOC Delay
6 back to List of setpoints
Subgroup: Voltage Protection
Setpoint group Generator settings Related FW 1.9.0
Range [units] Generator Overvoltage Wrn (page 246) .. 200 [%]
Default value 110 % Alternative config NO
Step 1 % of Nominal Voltage Ph-N (page 195) or Nominal Voltage Ph-Ph (page 195)
Comm object 8291 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator overvoltage protection. All three phases are checked. Maximum out of three is used.
Note: Phase to phase and phase to neutral voltages are used for this protection.
Generator Overvoltage Sd
6 back to List of setpoints