InteliLite Global Guide
350
Setpoint group Geo-Fencing Related FW 1.9.0
Range [units] HistRecOnl / Wrn / Sd / BOC[-]
Default value HistRecOnl Alternative config NO
Step [-]
Comm object 14611 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Protection type for geo-fencing 2 protection. Fence of circle area is adjusted by setpoint Fence Radius 2
(page 347). Delay for protection is adjusted by setpoint Fence 2 Delay (page 348).
HistRecOnl Position of gen-set is only measured and displayed on the LCD screen but not used
for protection. History record is made if position is out of Fence Radius 2 (page 347).
Wrn Position of gen-set is used for warning protection only. Protection is activated when
position of the gen-set is out of Fence Radius 2 (page 347).
Sd Position of gen-set is used for shutdown protection. Protection is activated when
position of the gen-set is out of Fence Radius 2 (page 347).
BOC Position of gen-set is used for BOC (Breaker Open and Cooling) protection. Protection
is activated when position of the gen-set is out of Fence Radius 2 (page 347).
Protection types
Note: Protection is activated also when GPS signal is lost for Fence 2 Delay (page 348).
Fence 2 Protection
6 back to List of setpoints
Group: Plug-In Modules
Setpoint group Plug-In Modules Related FW 1.9.0
Range [units] ENABLED / DISABLED [-]
Default value ENABLED Alternative config NO
Step [-]
Comm object 24280 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This setpoint enable or disable module in slot A.
Slot A
6 back to List of setpoints