235
Group: Protections
Subgroup: Overload Protection
Setpoint group Protections Related FW 1.9.0
Range [units] Enabled/Disabled/By LBI [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15664 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Overload protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints Overload BOC
(page 227), Overload Wrn (page 227) and Overload Delay (page 227).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 534).
Overload Protection
6 back to List of setpoints
Subgroup: Current Protection
Setpoint group Protections Related FW 1.9.0
Range [units] Enabled / Disabled / By LBI [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15665 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Short Circuit protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints Short Circuit
BOC (page 228) and Short Circuit BOC Delay (page 228).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 534).
Short Circuit Protection
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals