EasyManuals Logo

ComAp InteliLite AMF25 User Manual

ComAp InteliLite AMF25
735 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #217 background imageLoading...
Page #217 background image
InteliLite Global Guide
217
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 600 [s]
Default value 5 s Alternative config NO
Step s
Comm object 14683 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
When the value of fuel drop per hour is higher than Maximal Fuel Drop (page 216) this delay stars count
down. After count down of this delay alarm Wrn Fuel Theft (page 657) is activated.
Maximal Fuel Drop Delay
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. Fuel Pump Off (page 218) [%]
Default value 20 % Alternative config NO
Step 1 %
Comm object 10100 Related applications AMF, MRS
Config level Advanced
Setpoint visibility
Visible only if the logical binary output FUEL PUMP (PAGE 572) is configured and
logical binary input FUEL PUMP ON/OFF (PAGE 529) isn’t configured
Description
Threshold level for switching the binary output FUEL PUMP (PAGE 572) on.
Image 8.13 Fuel Pump On
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 529) is configured then binary
output FUEL PUMP (PAGE 572) is control by this binary input. Setpoints Fuel Pump On and
Fuel Pump Off (page 218) are not evaluated!
Note: Value from analog input has higher priority than ECU.
Note: This setpoint is visible only if the logical binary output FUEL PUMP (PAGE 572) is configured.
Fuel Pump On
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65