216
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 900 [s]
Default value 10 s Alternative config NO
Step 1 s
Comm object 14433 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if ECU is configuredd
Description
Delay for Fuel level which is send from ECU.
ECU Fuel Level Delay
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 10 000 [l]
Default value 200 l Alternative config YES
Step 1 l
Comm object 11103 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if the logical analog input FUEL LEVEL (PAGE 632) is or ECU is configured
Description
Define a capacity of gen-set fuel tank.
Fuel Tank Volume
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] Disabled / 1 .. 50 [%/h]
Default value 25 %/h Alternative config NO
Step 1%/h
Comm object 12373 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Setpoint indicates the maximum allowable drop of fuel in fuel tank per running hour. When the engine is not
running the maximal allowed fuel drop-off is preset to 5% of total tank volume per hour.
Maximal Fuel Drop