InteliLite Global Guide
215
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 900 [s]
Default value 10 s Alternative config NO
Step 1 s
Comm object 14343 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Visible only if the logical analog input FUEL LEVEL (PAGE 632) is configured or logical
binary input FUEL LEVEL (PAGE 529) is configured
Description
Delay for FUEL LEVEL (PAGE 632).
Fuel Level Delay
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] the range is defined by ECU sensor curve
Default value
the value is defined by
ECU sensor curve
Alternative config NO
Step the step is defined by ECU sensor curve
Comm object 14432 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if ECU is configured
Description
Warning threshold level for Fuel level which is send from ECU.
ECU Fuel Level Wrn
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] the range is defined by ECU sensor curve
Default value
the value is defined by
ECU sensor curve
Alternative config NO
Step the step is defined by ECU sensor curve
Comm object 14431 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if ECU is configured
Description
Shutdown or BOC threshold level for Fuel level which is send from ECU.
ECU Fuel Level Sd
6 back to List of setpoints