InteliLite Global Guide
203
Subgroup: Stopping Timers
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 3 600 [s]
Default value 30 s Alternative config NO
Step 1 s
Comm object 8258 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Runtime of the unloaded gen-set to cool the engine before stop.
Cooling Time
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 600 [s]
Default value 60 s Alternative config NO
Step 1 s
Comm object 9815 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Under normal conditions the engine must certainly stop within this period after the FUEL SOLENOID (PAGE
572) has been de-energized and the STOP SOLENOID (PAGE 598) energized. The Stop Solenoid output is
deactivated 12 s after last running engine indication went off.
Image 8.7 Stop Time 1
Stop Time

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals