InteliLite Global Guide
204
Image 8.8 Stop Time 2
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 3 600 [s]
Default value 180 s Alternative config NO
Step 1 s
Comm object 8662 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Runtime of engine after cooling pump. Binary output Cooling pump is closed when the engine starts and
opens AfterCool time delayed after gen-set stops.
After Cooling Time
6 back to List of setpoints
Subgroup: D+ Function
Setpoint group Engine settings Related FW 1.9.0
Range [units] Enabled / ChargeFail / Disabled [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 9683 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Behavior of D+ terminal.
D+ Function

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals