InteliLite Global Guide
198
Subgroup: Starting Timers
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0,0 .. 25,0 [s]
Default value 0,5 s Alternative config NO
Step 0,1 s
Comm object 10525 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Delay between FUEL SOLENOID (PAGE 572) and STARTER (PAGE 597) logical binary outputs.FUEL SOLENOID
(PAGE 572) is closed before STARTER (PAGE 597). Lead time is adjusted via this setpoint.
Image 8.2 Fuel Solenoid Lead
Note: LBO PRESTART (PAGE 585) goes to logical zero when Fuel Solenoid Lead goes to logical one.
Note: This setpoint is used only for diesel Fuel Solenoid (page 189)
Fuel Solenoid Lead
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 600 [s]
Default value 12 s Alternative config NO
Step 1 s
Comm object 9097 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Idle Time delay starts when RPM exceeds Starting RPM (page 191). Start fail is detected when during Idle
state RPM decreases below 2 RPM.
The output IDLE/NOMINAL (PAGE 582) remains inactive during the idle period. Binary output Idle/Nominal
opens during Cooling period again. This output can be used for switching the governor between idle and
Idle Time

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
BrandComAp
ModelInteliLite AMF25
CategoryController
LanguageEnglish

Related product manuals