InteliLite Global Guide
227
Group: Generator settings
Subgroup: Overload Protection
Setpoint group Generator settings Related FW 1.9.0
Range [units] Overload Wrn (page 227) .. 200 [%]
Default value 120 % Alternative config NO
Step 1 % of Nominal Power (page 176)
Comm object 8280 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold level for generator overload (in % of Nominal power) protection. Protection is BOC (Breaker Open
and gen-set Cooldown).
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Overload BOC
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.9.0
Range [units] 0 .. Overload BOC (page 227) [%]
Default value 120 % Alternative config NO
Step 1 % of Nominal Power (page 176)
Comm object 9685 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold level for generator overload (in % of Nominal power) protection. This is only warning.
Overload Wrn
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.9.0
Range [units] 0,0 .. 600,0 [s]
Default value 5,0 s Alternative config NO
Step 0,1 s
Comm object 8281 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Overload BOC (page 227)Overload BOC (page 227) and Overload Wrn (page 227) protection.
Overload Delay
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65