InteliLite Global Guide
226
Subgroup: Ventilation
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0–3600 [s]
Default value 30 s Alternative config NO
Step 1 s
Comm object 15767 Related applications MRS. AMF
Config level Advanced
Setpoint visibility
Only when logical binary output VENTILATION ON PULSE (PAGE 601) or VENTILATION
OFF PULSE (PAGE 600) is configured.
Description
This setpoint defines duration of pulse generated on logical binary outputs VENTILATION ON PULSE (PAGE
601) or VENTILATION OFF PULSE (PAGE 600) at the moment when logical binary output VENTILATION (PAGE
600) is activated or deactivated respectively.
Ventilation Pulse Time
6 back to List of setpoints
Subgroup: ECU Settings
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 100 [%]
Default value 50 % Alternative config NO
Step 1 %
Comm object 9948 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if ECU is configured
Description
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%. This setpoint
should be used only for Volvo Penta and Scania engines. It has no effect on other engine brands.
Note: To lock this setpoint against editing you also have to lock setpoint ECU Speed Adjustment 1
(page 342), ECU Speed Adjustment 2 (page 342) and ECU Speed Adjustment 3 (page 343).
ECU Speed Adjustment
6 back to List of setpoints