InteliLite Global Guide
209
Subgroup: Choke
Setpoint group Engine settings Related FW 1.9.0
Range [units] Disabled /Fixed Time / Temp Based [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 15717 Related applications MRS. AMF
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 597) is configured.
Description
This setpoint defines choke function behavior.
Disabled Choke function is disabled and logical binary output CHOKE (PAGE 597) is activated
under no circumstances.
Fixed Time Choke time is fixedly defined by Choke Time (page 209) setpoint.
Temp Based Choke time is calculated using actual engine (coolant) temperature. Setpoints Choke
Start Temp (page 210) and Choke Increment (page 211) are taken into
consideration.
Choke Function
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0–3600 [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 13011 Related applications MRS. AMF
Config level Advanced
Setpoint visibility
Only when LBO CHOKE (PAGE 597) is configured and setpoint Choke Function (page
209) = Fixed Time.
Description
Defines time logical binary output CHOKE (PAGE 597) is activated for when fixed time is used. When setpoint
Choke Function (page 209) is set to Temp Based value, Choke Time value have no effect.
Note: If setpoint Choke Lead (page 213) is set to nonzero value, total time the CHOKE output is
activated still matches value set by Choke Time setpoint. This mean Choke Timeshould be longer than
Choke Leadto ensure expected Choke behavior.