Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. Prestart Time [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 15774 Related applications MRS. AMF
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 597) is configured.
Description
This setpoint adjust the lead of logical binary output CHOKE. CHOKE (PAGE 597) is activated before logical
binary output STARTER (PAGE 633).
Note: In case Choke Lead is longer than 8s (cranking fail pause), Choke Lead will be limited to 8s
(cranking fail pause time). This limitation is applied only for cranking fail pause, Choke Lead in Prestart
stays unchanged.
Choke Lead
6 back to List of setpoints