InteliLite Global Guide
212
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 900 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 14430 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if ECU is configured
Description
Delay for Coolant temperature which is send from ECU.
ECU Coolant Temperature Delay
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] the range is define by sensor curve (analog or ECU)
Default value
the value is defined by
sensor curve (analog or
ECU)
Alternative config NO
Step the step is defined by sensor curve (analog or ECU)
Comm object 8688 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Visible only if the logical binary output TEMPERATURE SWITCH (PAGE 600) is
configured.
Description
Threshold level for switching the binary output TEMPERATURE SWITCH (PAGE 600) on.
Note: Value from analog input has higher priority than ECU.
Image 8.11 Temperature Switch
Temperature Switch On
6 back to List of setpoints