InteliLite Global Guide
208
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 255 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 14108 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Overspeed Overshot (page 207)
Description
Time for which is Overspeed Overshot (page 207) active. The timer starts in the same time when starter
starts.
Note: The setpoint is visible only, if Overspeed Overshot (page 207) is greater than 0.
Overspeed Overshot Period
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 12895 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input OIL PRESSURE (PAGE 634) is configured
Description
Warning or history threshold level for OIL PRESSURE (PAGE 634).
Oil Pressure Wrn
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 12779 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input OIL PRESSURE (PAGE 634) is configured
Description
Shutdown threshold level for OIL PRESSURE (PAGE 634).
Oil Pressure Sd