Loading...
InteliLite Global Guide
207
Setpoint group Engine settings Related FW 1.9.0
Range [units] 0 .. 600 [s]
Default value 2 s Alternative config NO
Step 1 s
Comm object 8394 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Time of closing of the PRESTART (PAGE 621) output prior to the engine start. Set to zero if you want to leave
the output PRESTART (PAGE 621) open.
Image 8.1 Prestart Time
Prestart Time
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.9.0
Range [units] 5 .. 50 [%]
Default value 25% Alternative config NO
Step 1 % of Nominal RPM (page 197)
Comm object 8254 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the “firing” speed level as percent value of the Nominal RPM (page 197). If this level
is exceeded the engine is considered as started.
Starting RPM
6 back to List of setpoints